HV test units HighPerformance F1-1B / F1-1N

200 .. 3.500 V AC, 300 .. 7.000 V AC

The multi-coloured touch panel enables ergonomic operation of the test units, which are equipped with a serial RS-232-C port as standard (optionally available: Ethernet or USB). All units are also available without a control module for easy integration with automated systems.

Modular hi-pot test unit

A range of unit variants with various output voltages are available, depending on the use case. The optional expansion modules enable the individual configuration of your system.

With Touch-Panel: F1-1B
Without Touch-Panel: F1-1N

  • 19” slide-in system
  • High-quality metal housing
  • Access lock via configurable password entry stage
  • Service-friendly – can be replaced in just a few steps
  • Interfaces: RS-232-C; Ethernet or USB as alternatives

Test voltage

200 … 3,500 V AC, 300 … 7,000 V AC, 300 … 4,500 V DC (optional), 400 … 9,000 V DC (optional)

Voltage ramp

User-programmable for start and end of test

Nominal capacity

500 VA

Trip current

0 … 1/10/70 mA

Interface

RS-232-C

Line voltage

230 V, +/−10%; 49 … 51 Hz*

Form factor

19”/4 RU

DC voltage

Test voltage: 300 … 4,500/9,000 VDC
Trip current: 0 … 1/10/70 mA

Insulation resistance

0.1 … 1/10/100 MΩ + auto-range

Safety current limiter

<3 mA with AC; <5 mA with DC

Voltage read-back

Module enables four-wire measurement by read-back of test voltage

Burn function

Overcurrent tripping can be deactivated for troubleshooting

Additional digital outputs

6 digital outputs for controlling an external switchover matrix

Ethernet

Alternative interface instead of RS-232-C port

USB

Alternative interface instead of RS-232-C port

Software package

Elution® Device software package

  • 93-1B housing 19”/4 RU
  • Mobile Primus Basic test unit
  • Test gun 94-2A
  • Warning lamp F9-1A
  • Two-hand control F9-1L-01
  • Footswitch F9-1D
  • Test cage 94-3A/B
  • Dummy module 94-2M Z01
Overview

We respect your privacy

We use cookies to offer you an ideal experience on our website. This includes cookies that are necessary to operate our web pages as well as cookies only used for anonymous statistical purposes, for user experience settings and for displaying customised content. You can decide which categories you want to allow. Please note that based on your settings, not all the functionalities of our site may be available.

Cookie settings

 

Without these cookies, the website cannot function correctly.

 

These cookies are used to analyse user behaviour on our website. They may count how often a user has visited the site or how long they spend on a certain web page.

 

These cookies are used to improve our website’s user experience. They may store whether you have already accessed a Google Maps map so that you won’t be shown our privacy statement again.